1 .. _stretch_mode:
2
3 ================
4 Stretch Clusters
5 ================
6
7
8 Stretch Clusters
9 ================
10 Ceph generally expects all parts of its network and overall cluster to be
11 equally reliable, with failures randomly distributed across the CRUSH map.
12 So you may lose a switch that knocks out a number of OSDs, but we expect
13 the remaining OSDs and monitors to route around that.
14
15 This is usually a good choice, but may not work well in some
16 stretched cluster configurations where a significant part of your cluster
17 is stuck behind a single network component. For instance, a single
18 cluster which is located in multiple data centers, and you want to
19 sustain the loss of a full DC.
20
21 There are two standard configurations we've seen deployed, with either
22 two or three data centers (or, in clouds, availability zones). With two
23 zones, we expect each site to hold a copy of the data, and for a third
24 site to have a tiebreaker monitor (this can be a VM or high-latency compared
25 to the main sites) to pick a winner if the network connection fails and both
26 DCs remain alive. For three sites, we expect a copy of the data and an equal
27 number of monitors in each site.
28
29 Note that the standard Ceph configuration will survive MANY failures of the
30 network or data centers and it will never compromise data consistency. If you
31 bring back enough Ceph servers following a failure, it will recover. If you
32 lose a data center, but can still form a quorum of monitors and have all the data
33 available (with enough copies to satisfy pools' ``min_size``, or CRUSH rules
34 that will re-replicate to meet it), Ceph will maintain availability.
35
36 What can't it handle?
37
38 Stretch Cluster Issues
39 ======================
40 No matter what happens, Ceph will not compromise on data integrity
41 and consistency. If there's a failure in your network or a loss of nodes and
42 you can restore service, Ceph will return to normal functionality on its own.
43
44 But there are scenarios where you lose data availability despite having
45 enough servers available to satisfy Ceph's consistency and sizing constraints, or
46 where you may be surprised to not satisfy Ceph's constraints.
47 The first important category of these failures resolve around inconsistent
48 networks -- if there's a netsplit, Ceph may be unable to mark OSDs down and kick
49 them out of the acting PG sets despite the primary being unable to replicate data.
50 If this happens, IO will not be permitted, because Ceph can't satisfy its durability
51 guarantees.
52
53 The second important category of failures is when you think you have data replicated
54 across data centers, but the constraints aren't sufficient to guarantee this.
55 For instance, you might have data centers A and B, and your CRUSH rule targets 3 copies
56 and places a copy in each data center with a ``min_size`` of 2. The PG may go active with
57 2 copies in site A and no copies in site B, which means that if you then lose site A you
58 have lost data and Ceph can't operate on it. This situation is surprisingly difficult
59 to avoid with standard CRUSH rules.
60
61 Stretch Mode
62 ============
63 The new stretch mode is designed to handle the 2-site case. Three sites are
64 just as susceptible to netsplit issues, but are much more tolerant of
65 component availability outages than 2-site clusters are.
66
67 To enter stretch mode, you must set the location of each monitor, matching
68 your CRUSH map. For instance, to place ``mon.a`` in your first data center ::
69
70 $ ceph mon set_location a datacenter=site1
71
72 Next, generate a CRUSH rule which will place 2 copies in each data center. This
73 will require editing the CRUSH map directly::
74
75 $ ceph osd getcrushmap > crush.map.bin
76 $ crushtool -d crush.map.bin -o crush.map.txt
77
78 Now edit the ``crush.map.txt`` file to add a new rule. Here
79 there is only one other rule, so this is ID 1, but you may need
80 to use a different rule ID. We also have two datacenter buckets
81 named ``site1`` and ``site2``::
82
83 rule stretch_rule {
84 id 1
85 type replicated
86 min_size 1
87 max_size 10
88 step take site1
89 step chooseleaf firstn 2 type host
90 step emit
91 step take site2
92 step chooseleaf firstn 2 type host
93 step emit
94 }
95
96 Finally, inject the CRUSH map to make the rule available to the cluster::
97
98 $ crushtool -c crush.map.txt -o crush2.map.bin
99 $ ceph osd setcrushmap -i crush2.map.bin
100
101 If you aren't already running your monitors in connectivity mode, do so with
102 the instructions in `Changing Monitor Elections`_.
103
104 .. _Changing Monitor elections: ../change-mon-elections
105
106 And lastly, tell the cluster to enter stretch mode. Here, ``mon.e`` is the
107 tiebreaker and we are splitting across data centers. ``mon.e`` should be also
108 set a datacenter, that will differ from ``site1`` and ``site2``. For this
109 purpose you can create another datacenter bucket named ```site3`` in your
110 CRUSH and place ``mon.e`` there ::
111
112 $ ceph mon set_location e datacenter=site3
113 $ ceph mon enable_stretch_mode e stretch_rule datacenter
114
115 When stretch mode is enabled, the OSDs will only take PGs active when
116 they peer across data centers (or whatever other CRUSH bucket type
117 you specified), assuming both are alive. Pools will increase in size
118 from the default 3 to 4, expecting 2 copies in each site. OSDs will only
119 be allowed to connect to monitors in the same data center. New monitors
120 will not be allowed to join the cluster if they do not specify a location.
121
122 If all the OSDs and monitors from a data center become inaccessible
123 at once, the surviving data center will enter a degraded stretch mode. This
124 will issue a warning, reduce the min_size to 1, and allow
125 the cluster to go active with data in the single remaining site. Note that
126 we do not change the pool size, so you will also get warnings that the
127 pools are too small -- but a special stretch mode flag will prevent the OSDs
128 from creating extra copies in the remaining data center (so it will only keep
129 2 copies, as before).
130
131 When the missing data center comes back, the cluster will enter
132 recovery stretch mode. This changes the warning and allows peering, but
133 still only requires OSDs from the data center which was up the whole time.
134 When all PGs are in a known state, and are neither degraded nor incomplete,
135 the cluster transitions back to regular stretch mode, ends the warning,
136 restores min_size to its starting value (2) and requires both sites to peer,
137 and stops requiring the always-alive site when peering (so that you can fail
138 over to the other site, if necessary).
139
140 Stretch Mode Limitations
141 ========================
142 As implied by the setup, stretch mode only handles 2 sites with OSDs.
143
144 While it is not enforced, you should run 2 monitors in each site plus
145 a tiebreaker, for a total of 5. This is because OSDs can only connect
146 to monitors in their own site when in stretch mode.
147
148 You cannot use erasure coded pools with stretch mode. If you try, it will
149 refuse, and it will not allow you to create EC pools once in stretch mode.
150
151 You must create your own CRUSH rule which provides 2 copies in each site, and
152 you must use 4 total copies with 2 in each site. If you have existing pools
153 with non-default size/min_size, Ceph will object when you attempt to
154 enable stretch mode.
155
156 Because it runs with ``min_size 1`` when degraded, you should only use stretch
157 mode with all-flash OSDs. This minimizes the time needed to recover once
158 connectivity is restored, and thus minimizes the potential for data loss.
159
160 Hopefully, future development will extend this feature to support EC pools and
161 running with more than 2 full sites.
162
163 Other commands
164 ==============
165 If your tiebreaker monitor fails for some reason, you can replace it. Turn on
166 a new monitor and run ::
167
168 $ ceph mon set_new_tiebreaker mon.<new_mon_name>
169
170 This command will protest if the new monitor is in the same location as existing
171 non-tiebreaker monitors. This command WILL NOT remove the previous tiebreaker
172 monitor; you should do so yourself.
173
174 If you are writing your own tooling for deploying Ceph, you can use a new
175 ``--set-crush-location`` option when booting monitors, instead of running
176 ``ceph mon set_location``. This option accepts only a single "bucket=loc" pair, eg
177 ``ceph-mon --set-crush-location 'datacenter=a'``, which must match the
178 bucket type you specified when running ``enable_stretch_mode``.
179
180
181 When in stretch degraded mode, the cluster will go into "recovery" mode automatically
182 when the disconnected data center comes back. If that doesn't work, or you want to
183 enable recovery mode early, you can invoke ::
184
185 $ ceph osd force_recovery_stretch_mode --yes-i-really-mean-it
186
187 But this command should not be necessary; it is included to deal with
188 unanticipated situations.
189
190 When in recovery mode, the cluster should go back into normal stretch mode
191 when the PGs are healthy. If this doesn't happen, or you want to force the
192 cross-data-center peering early and are willing to risk data downtime (or have
193 verified separately that all the PGs can peer, even if they aren't fully
194 recovered), you can invoke ::
195
196 $ ceph osd force_healthy_stretch_mode --yes-i-really-mean-it
197